ETH IO-3.0 is an Ethernet I/O unit for monitoring analog and digital inputs and controlling relay outputs over a LAN, with 8 analog inputs, 8 digital inputs and 8 potential free relay contacts in a single box. It posts data over HTTP on the LAN, with GSM/GPRS (2G or 3G) optional, and is configured through its web page or Telnet. The 8 digital inputs take 5-24 V DC with 3750 V RMS isolation. The analog inputs are 4-20ma single ended 2CH, 0-5V I/P 3CH, 0-12V I/P 2 CH and 0-100V I/P 1CH. The 8 relay outputs have normally close, normally open and common contacts rated 1A at 120V AC or 1A at 24V DC. The LAN runs at 10/100 Mbps over TCP/IP, and the RS 232 serial config port uses 2400 baud, 8 data bits, "No Parity", 1 stop bit and flow control "None". A 16X2 alphanumeric LCD with backlight and an internal battery are optional. Power is 12 V DC, 1 Amp, with fuse and reverse polarity protection. LEDs show power (green), connection establishment (yellow), digital data and relay status (red) and GSM status (green). The black enclosure marked ETH I/O 3.0 carries indicators R 1 to R 8 and I/P1 to I/P12, with a green terminal block marked 5V A1 A2 A3 A4 A5 A6 A7 A8 G, a LAN port and an RS 232 connector on one side. It operates at 0 to 55°C, stores at -40 to 85°C, measures 205 mm (L) x 130 mm (W) x 30 mm (H), weighs 825 g and has a 12 Months warranty for the box product. Uses include industrial control and automation, environment monitoring and control, plant automation, building management systems (BMS), remote data logging, ATM management and mobile tower management, with sensors such as humidity, temperature, smoke and door sensors. Part numbers: ETH IO-3.0 - 1 (8DI-8AI-8RLY2G1602D MB), ETH IO-3.0 - 2 (8DI-8AI-8RLY3G1602D MB)